تحليل جودة الطاقة الكهربائية في شبكة خط معفى من التقنين/دراسة حالة في طرطوس/

Authors

  • ضحى خالد جديد جامعة طرطوس، كلية الهندسة التقنية، قسم هندسة الأتمتة الصناعية-
  • محمد علي الديري هندسة نظم القدرة الكهربائية-جامعة حلب،

Keywords:

Harmonics, Total Harmonic Distortion (THD), Voltage Balance, Electrical Network Structure, Power Factor

Abstract

This research evaluates and analyzes the power quality in a private network supplying a tourism facility in Tartous Governorate. The study focuses on indicators such as harmonics, power factor, voltage and current balance, and Total Harmonic Distortion (THD). The aim is to identify the causes of power quality deterioration and assess how these issues affect the connected equipment within this specialized electrical network. Additionally, the study investigates how this impact propagates through linking transformers to other facilities connected to the hot line. Measurements were conducted using a Power Analyzer to analyze the effects of nonlinear loads, such as electronic devices and air conditioning systems, on the network and its connected equipment. The results revealed high harmonic levels, particularly in the first phase, leading to reduced power quality and increased temperatures in electrical equipment. It was also observed that imbalance and uneven distribution of loads across phases increase the likelihood of faults and elevate operational costs.

Downloads

Published

2026-10-29