Study the effect of combined action of safety valve with air valves and pressure tanks in mitigating water shock

Authors

  • عادل جرجي كلية الهندسة المدنية- قسم الموارد المائية – جامعة حمص
  • شذى خلوف كلية الهندسة المدنية – قسم الموارد المائية – جامعة حمص

Keywords:

Water shock - Safety valve - Air valves - pressure tank.

Abstract

The research included a descriptive study of the phenomenon of water shock resulting from sudden pump stoppages, which poses dangerous effects on pumping lines and water networks. Valve types were also defined, and the combined effect of safety valves, air valves, and pressure tanks on the pressure values ​​resulting from hydraulic shock was explained, with the aim of protecting the water network from high pressure values. This was done by developing several scenarios that demonstrate the impact of this joint effort on the network using the( Bently Hammer) program along a pumping line extending from the Markieh pumping station 3 towards the Qamsiyeh reservoir in Tartous Governorate. It was concluded that the safety valve neither affects nor improves the minimum negative pressures. Furthermore, the presence of a compressed air tank eliminates the need for all other protective devices, such as a safety valve and an air valve, as they can alone reduce the maximum pressures. Furthermore, the combined action of the air valve and the safety valve leads to minimal protection of the pumping line in the event that a compressed air tank is not available.